| Technical specification | |
| Genset Model | GP2063PS |
| Prime Power | 1500KW/1875KVA |
| Standby Power | 1650KW/2063KVA |
| Phase Number | 3 |
| Power Factor | 0.8 |
| Rated Voltage | 230/400V |
| Frequency | 50 HZ |
| Rated Current | 2706A |
| Genset Structure | SILENT |
| Dimension | 12192×2435×2896mm |
| Net Weight | 15000KG |
| Noise level | 85dB at 7 meters |
| Fuel Tank Capacity | / |
| Engine Model | 4016TAG1A |
| Engine Features | 16-cylinder,4 stroke,water cooled ,Turbo |
| Bore * Stroke | 160mm × 190mm |
| Displacement | 61L |
| 12-hour Power(kw) | 1588KW/1500 |
| Fuel Consumption L/H | 379.5L/H |
| Compression Ratio | 16:01 |
| Governor type | Electric |
| Alternator Model | STAMFORD /PI734E |
| Excitation Mode | brushless self-excited |
| Insulation Class | H |
| Protection Class | IP23 |
| Construction Type | SAE Disc-coupling |
| Controler panel | |
| Smartgen 6120 | intelligent and network techniques is used for automatic control system of diesel generator. It can carry out functions including automatic start/stop, data measure and alarming.automatic switching control functions (AMF), especially suitable for the automation system composed by Mains and Generator |
![]()
![]()